Selecting an access control power supply starts with three questions: what voltage each lock and controller permits, how much current is needed during actuation, and which functions must remain available when mains fails. Then check the supply, battery, control contacts, enclosure and wiring as one system.
This guide follows load sizing, output selection, backup, wiring and acceptance checks, using the original Sanyi Power MJ-60A/MJ-60B datasheets to distinguish real configurations. Numerical examples below illustrate calculations; they are not measured lock specifications, customer cases or runtime promises.
1. Separate lock-control supplies, EPS backup and power boxes
| Product direction | Check first | Do not assume from its name |
|---|---|---|
| Access control supply | Lock control, output channels and battery management | NO/NC contacts, delay or permissible load per channel |
| EPS DC backup supply | Float charging, mains/battery selection and circuit count | Dedicated lock contacts or equivalence to high-power building AC EPS |
| Access control power box | Module, terminals, installation and battery space | An included battery, electrical compatibility or guaranteed runtime |
For normally open/closed lock control, verify that the exact model specifies the function. For multiple DC circuits requiring backup, compare the 43/53/63 EPS DC backup range. Review access control power boxes for cabinet requirements, while checking battery compatibility independently of physical space.
2. Build a load schedule before choosing amperes
| Required information | Why it matters |
|---|---|
| Exact device and allowable input range | Nominal 12V or 24V is not the full permitted range |
| Hold and actuation current | Steady and transient loads can differ |
| Simultaneous actions and duration | Establishes the worst load step |
| Functions required during an outage | Defines the battery discharge load |
| One-way cable distance and conductor size | Determines voltage at the equipment, not just the PSU |
| Circuit separation and interlock requirements | Defines control contacts and fault interactions |
Start with Steady load current = sum of actual steady currents. As a calculation example, two locks at 0.5A each, a 0.3A controller and readers totaling 0.2A produce a 1.5A steady load. Any additional actuation peaks must be checked for amplitude, simultaneous operation and duration. The 1.5A result is not an all-conditions limit.
After mains returns, the supply may power the load while charging the battery. Check that combined operating condition when sizing the PSU. During an outage, calculate battery capacity from the discharge load; do not add mains-restoration charging current again as battery discharge current.
3. A 12V label does not establish compatibility with every output
PSU output, permitted equipment input and battery-bus voltage are different quantities. Backup systems may use a charging voltage above the battery nominal voltage. The connected equipment must tolerate the actual range.
For example, MJ-60B lists a 13.8V main output V1, an independent 12V output V2 and a 13.8V charging channel V3. These are not three interchangeable 12V load terminals. Check the lock, controller and reader limits before connecting nominal 12V equipment to 13.8V.
For 24V equipment, select a compatible output and backup architecture. The MJ-60A 21V or 30V columns must not be advertised as a universal 24V output; confirm the exact configuration, adjustment range and charging arrangement.
4. MJ-60A vs MJ-60B: compare channels and control
| Item | MJ-60A | MJ-60B |
|---|---|---|
| Voltage information | 13.8V, 21V and 30V columns; confirm the configuration | V1: 13.8V; V2: 12V; V3: 13.8V charging |
| Lock control | Check the selected A-version diagram | Explicit NO/NC function |
| Release delay | Do not import B-model functions | Adjustable 0–15s |
| Independent 12V channel | Verify the applicable configuration | V2 is 12V/1A; the datasheet describes camera use |
| Battery charging | Check the applicable voltage-column data | V3 is 13.8V/1A; listed discharge protection is 10.5V |
| Operating boundary | Check voltage, current and rated power together | Review main, auxiliary and charging loads together |
Sources: MJ-60A original PDF and MJ-60B original PDF. Both documents list 100–240Vac, 50/60Hz input and describe short-circuit, overload, overvoltage and battery over-discharge functions. Confirm protection mode, wiring, rated-power limits and certification scope for the supplied revision. Adding current columns does not establish a guaranteed total output rating.
5. Wiring: distinguish power terminals from control terminals
With power isolated, use the exact model diagram to identify:
- mains L/N and protective earth FG;
- load polarity and the permitted current of each channel;
- battery BAT polarity and the charging connection;
- NO/NC, COM and release-control terminals;
- the control relationship between lock, controller and exit devices.
Terminal order and logic can change between models. Do not wire by enclosure appearance. NO/NC contacts, a lock's unpowered state and project interlocks are also different concepts. Qualified personnel should confirm installation and testing against device instructions, system design and applicable project requirements.
6. Battery sizing: separate an assumption from a runtime promise
A first capacity estimate is:
Theoretical Ah ≈ outage load current × target hours ÷ usable-capacity factor
For an example 1.5A outage load, a 4-hour target and an assumed 0.7 usable factor, capacity is approximately 1.5 × 4 ÷ 0.7 = 8.6Ah. Four hours and 0.7 are calculation assumptions, not universal requirements or battery guarantees.
The final selection must consider chemistry, temperature, ageing, discharge rate, low-voltage cut-off, cable losses and recharge time. Establish the target from the project and required functions. Requirements applying to one type of fire-alarm equipment must not be transferred to an entire access control installation without verifying scope.
7. Check voltage drop at the worst operating point
For a simple DC circuit, start with Voltage drop = load current × loop resistance. Loop resistance includes both outgoing and return conductors.
An example 0.4Ω loop carrying 1.5A drops 0.6V. A correct PSU-terminal reading does not prove that the lock receives sufficient voltage. Check the battery-low bus, actuation peaks, connector resistance and cable temperature too.
Use the voltage-drop calculator for an initial estimate and measure at the real load. Before increasing system voltage, confirm that every device and control interface accepts it. Arbitrary voltage adjustment does not repair an undersized cable.
8. Acceptance checks must cover mains, outage and recovery
| Test stage | Observe | Record |
|---|---|---|
| Normal mains and lock actions | Channel/device voltage, actuation current and controller resets | Load schedule and measured waveforms or readings |
| Mains removal | Battery operation, required functions and continuity | Load, battery condition, duration and environment |
| Mains restoration | Load plus battery charging and any repeated transfer | Charging current, temperature and recovery |
| Control and delay | NO/NC logic, delay and project interlocks | Exact terminal diagram and settings |
| Protection and recovery | Datasheet-defined response and reset | Qualified testing under an approved procedure |
Hold-up time is not mains-to-battery transfer time and does not guarantee that a particular controller will avoid restarting. Validate the exact supply/battery/load combination. Check certification and EMC scope for the model, market and final system rather than assuming that a displayed mark covers every configuration.
FAQ
Does every access control power supply require the same certification?
No single label establishes suitability for every project. Check the location, final system, specification and authority requirements, then verify valid documents covering the exact configuration. A test-standard reference in a datasheet is not proof that every version has the corresponding certification.
Must an access control battery provide four hours of backup?
Do not treat four hours as a universal requirement. Establish the functions, project requirements and interlocks first, then size the battery and recharge arrangement. The duration in this guide is an example only.
Can door locks and cameras use the same supply?
Check channels and system design. MJ-60B explicitly describes an independent 12V output for camera use, but its 1A channel limit, total power, transients and fault interactions still need verification. Neither compulsory sharing nor a blanket prohibition is appropriate for every installation.
How should I choose between an access control supply and EPS backup?
For lock control, check NO/NC, release delay and interfaces. For multi-circuit DC backup, compare the 43 Series EPS selection data and complete EPS range. A battery connection alone does not make the products interchangeable.
What helps obtain the right configuration and quotation?
Send equipment models, allowable voltage, steady/actuation current, cable distances, battery/runtime target, cabinet space and quantity. Review original documents on the MJ access control supply page, then contact Sanyi Power. Pricing, delivery and after-sales arrangements follow the specific product and mutually confirmed order.